- ویژگی سازندهلوله
The twin furnace Maxecon boiler for industrial steam or hot water applications is a high quality, reliable boiler with many years operational experience coupled with a record of highly effeicient performance and reliability. More than 500 single ortwin furnace Maxecon boilers continue to provide a dependable and efficient service to industry.
When fitted with special control panels single furnace firing for indefinite periods is available. This feature in addition to providing very high turn down ratios permits maintenance work to be carried out on each burner in turn whilst boiler output is maintained at up to 50% of normal rated output on the other furnace.
Superheat
Units can be supplied with superheaters to suit specific applications.
Design
All oil or gas fired Maxecon boilers are designed and constructed in accordance with BS 2790 and meet the requirments of all leading insurance companies.
Fuel
Natural gas, LPG or oil up to a viscosity at 6,500 sec. Redwood No. 1.
Furnaces
Cylindrical, fully corrugated furnaces of welded construction are attached to each reversal chamber and the boiler front plate by welding.
Tubes
Tubes are 63.5mm diameter. Stay tubes are welded in. Plain tubes are expanded and are seal welded in the reversal chambers.